Quick answer: Rheem hybrid (heat pump) water heaters show four-character codes that start with A (alarm) or T (alert). The first thing to know about any code is whether you still have hot water. Heat pump faults such as A004, A108 or A105 switch the heater to its electric elements, so you keep hot water but pay much more to heat it. Element, tank-sensor and over-temperature faults such as A125, A103 or A200 shut the heater off. Find your code in the table below.
Before anything else: 3 steps that solve or narrow down most codes
- Read the full code, then write it down. On Gen V units, press Next until "Current Alarm" appears, then press the Down arrow to scroll through every active code. A unit can show more than one at a time.
- Answer one question: is the water hot, lukewarm, or cold? That tells you which group your code is in (see the decision guide below).
- Clear the alarm once and watch. Press Clear Alarm. If the code comes back within hours, the fault is real. If it never returns, it was a one-time event, such as a brief power dip or a clogged filter you've since cleaned.
Hot, lukewarm or cold? Find your code group in 10 seconds
💧 Water is hot, but the bill went up
You probably have a heat pump fault (A004–A009, A101, A102, A105, A106, A108). The heater has fallen back to its elements. It's not urgent, but it costs money every day you leave it.
🌡️ Water is lukewarm or runs out fast
Look for T132 (can't keep up with demand), T131 (dirty filter), or the unit being in Heat Pump mode, which recovers very slowly.
❄️ Water is cold
You likely have a heater-disabled code: A008, A103, A104, A125–A129 or A200, or A130 (unit off). Turn off the breaker before opening anything.
Every Rheem hybrid error code (Gen V)
This table comes from the troubleshooting chart in Rheem's current Gen V Universal Connect manual (AP23657 Rev 01). Type your code, or filter by what's happening to your hot water.
| Code | What it means | Hot water? | What you can do | What a pro does |
|---|---|---|---|---|
A004 | Compressor shutdown: discharge–suction trip | Elements | Clean the air filter; make sure nothing blocks the top vents | Confirms the fan runs with the compressor on; checks for oily residue (refrigerant leak) |
A005 T005 | Discharge temperature high, usually from low airflow | Elements | Clean the filter; check the room isn't too small or closed up | Tests the fan, ducting and airflow |
A006 T006 | Suction temperature too low | Elements | Clean the filter; check room temperature | Compressor and sealed-system checks |
A009 T009 | Compressor wiring may be faulty | Elements | None, call a pro | Checks wiring and sensor plugs; reads sensors in the Service menu |
A008 | Dry fire: not enough water in the tank | Heater off | Make sure the cold supply valve is open; run a hot faucet until air stops sputtering | If the code keeps returning, looks for trapped air or a supply problem |
A101 A102 A105 A106 | Suction, ambient, evaporator or discharge sensor failure | Elements | None, call a pro | Measures the thermistor's resistance. In the Service menu, −40°F means an open circuit and +250°F means a short |
A103 A104 | Lower or upper tank temperature sensor failure | Heater off | None, call a pro | Tests and replaces the tank sensor |
A107 | Water detected on the floor (leak sensor) | Heating stops | Find the water. Dry the rope sensor. Use the 24-hour override (hold Clear Alarm 5 seconds) only after you've confirmed there's no leak | Replaces the rope sensor; replaces the board if the alarm stays with a dry or new sensor |
A108 | Condensate blocked: unclog the line | Elements | Clear the condensate line (full A108 guide) | If the pan is dry and the line is clear, replaces the condensate sensor |
A125 A126 | Lower or upper element error, or relay stuck closed | Heater off | Turn off the breaker | Measures element resistance: a bad reading means a new element, a good one means a new board |
A127 | Element wire routing error | Heater off | Turn off the breaker | Checks the wires at the element and the board, then tests the element |
A128 A129 | Lower or upper element relay won't close | Heater off | Turn off the breaker | Checks wiring and resistance, then replaces the board or relay |
A130 | Unit off, or air temperature freezing | Off until you act | Select a mode to turn the unit back on; warm the room if it's near freezing | Not usually needed |
T131 | Clean filter reminder | Reminder only | Switch to Electric or Off, wash the filter in mild detergent, dry it fully, put it back, restore your mode | Not needed |
T132 | Difficulty keeping up with demand | Runs short | Check for a running tap or hidden leak; try Energy Saver or High Demand mode | Checks whether the tank is too small for the household |
A120–A123 | Shut-off valve: can't close, can't open, input error, or not installed | Check display | Unplug and re-seat the valve plug. No valve fitted? Set the shut-off valve option to NO | Checks the wiring, then contacts Rheem |
A200 | High water temperature: the ECO (safety cut-off) tripped | Heater off | Turn off the breaker. Don't keep resetting it | Checks the elements for a short to ground and the sensor resistance, then the board |
T300 | Water leak sensor not installed | Check display | Find the rope sensor and plug it back in | Tests sensor resistance to tell a bad sensor from a bad board |
A502 A503 T504 | Clock needs programming, clock not advancing, Wi-Fi chip communication error | Check display | Power-cycle once at the breaker | The manual calls for a new control board |
A900–A905 T901 | Controller faults | Check display | Power-cycle once, then call | Board diagnosis or replacement |
A906 | Power board temperature-protection sensor failure (controller overheating) | Check display | Make sure the top of the unit isn't covered or boxed in | Board replacement |
"Check display" means the manual doesn't say how heating behaves with that code active. Check whether your water is still hot.
⚠️ Older Rheem hybrids: the same code number can mean something different
Most code lists online skip this, and it's the most common reason people order the wrong part. Rheem has changed its code numbering over the years. On older hybrid models (manual AP16697), the A100-series codes cover completely different faults than they do on Gen V:
| Code | Older hybrid (AP16697) | Gen V (AP23657) |
|---|---|---|
A101 | Upper temperature thermistor failure | Suction temperature sensor failure |
A102 | Water sensor alarm (water in drain pan) | Ambient temperature sensor failure |
A103 | No water in tank: fill tank | Lower tank temperature sensor failure |
A104 | ECO (high-limit cut-off) activated | Upper tank temperature sensor failure |
A105 | Lower element error | Evaporator temperature sensor failure |
How to tell which you have: Gen V units have physical Mode, Next, Clear Alarm and Wi-Fi buttons and a "!" warning icon. Older units have a different control panel, and the model's manual number is printed at the bottom of every page of your Use & Care guide. The manual tucked in the pocket on the side of the heater is the final word for your exact unit.
Codes you'll see online that aren't US Rheem hybrid codes
If you've seen Rheem codes like E0–E8, F01–F13, P01–P07 or Fd, they come from Australian Rheem heat pumps (AmbiPower and AmbiHeat models), which use a different control system. US Rheem hybrids, including ProTerra, Performance Platinum and the 120V plug-in, use A-codes and T-codes. If your display shows a two-character code, you may have a different Rheem product, such as a tankless or gas unit. Codes like "HP01" that show up on some blogs don't appear in Rheem's US hybrid manuals at all.
The most common code: how to fix A108 (condensate blocked)
A heat pump pulls moisture out of the air, much like an air conditioner. That water drains out through a condensate line. When algae, dust or a kinked hose blocks the line, water backs up and touches a sensor, and you get A108. It takes about 10 minutes to fix:
- Turn the heater off at the breaker.
- Follow the condensate hose from the top of the unit to where it drains: a floor drain, a pump, or outside.
- Check for kinks, sags that hold water, or an outlet sitting in water. Rheem calls for lines pitched downward at least 1/8 inch per foot.
- Use a wet/dry vacuum on the drain end to suck the clog out. Don't blow compressed air back into the unit.
- Pour a cup of household bleach into the condensate opening to kill algae, and confirm it drains freely. Rheem recommends doing this once a year.
- Restore power and press Clear Alarm. If A108 comes back with a clear line and a dry pan, the condensate sensor itself has likely failed.
What each code is costing you while you wait
Rheem rates its own modes, which shows why element-only codes are worth fixing quickly:
| Mode | Efficiency | Recovery speed | When to use it |
|---|---|---|---|
| Energy Saver (default) | Very high | Fast | Best everyday setting |
| Heat Pump | High | Very slow | Small households with steady use |
| High Demand | Low | Very fast | Guests, or a big bath day |
| Electric | Very low | Fast | Only while a heat pump fault is being fixed |
| Vacation | Very high | None | Away from home |
When a heat pump code forces the unit onto its elements, it's effectively in Electric mode, the least efficient setting. A standard 4,500-watt element draws about 18.75 amps at 240 volts, which is why an element-only month can show up on your bill even though the water feels normal.
Technician reference: element and sensor checks
For element codes (A125–A129), the test is element resistance with the power off and the wires disconnected. Expected resistance is volts² ÷ watts:
- 4,500 W element at 240 V: about 12.8 Ω
- 3,800 W element at 240 V: about 15.2 Ω
- An infinite (open) reading means the element is broken. Any continuity from a terminal to the tank means it's shorted to ground, a common cause of both A200 and a tripping breaker.
- On 208 V supply, the same 4,500 W element produces only about 3,380 W, so recovery is slower even with nothing wrong.
For sensor codes, Rheem's Service menu reads a disconnected (open) thermistor as −40°F and a shorted one as +250°F. That's a fast way to confirm a sensor fault before you open the cabinet.
Prevent most codes: the yearly maintenance checklist
Most heat pump codes come down to airflow or drainage. Here's a routine built from Rheem's manual, in one list:
- Whenever T131 appears (we suggest checking every 3 months): wash the air filter.
- Monthly: drain a few quarts from the tank's drain valve to clear sediment.
- Once a year: pour a cup of bleach into the condensate line and check that it drains freely.
- Once a year: lift and release the relief (T&P) valve lever and let several gallons flush through.
- Keep the space open: at least 6 inches above the unit, and about 700 cubic feet of air around it. That's about a 9 × 10 ft room with an 8 ft ceiling. Smaller rooms need louvered doors or vents.
- Watch the room temperature: the unit needs to stay above freezing. If the room cools by more than 15°F while the heat pump runs, it needs more air circulation.
- After two weeks away: run a hot faucet for several minutes before using appliances on the hot water line. Rheem warns that hydrogen gas can build up in an unused tank.
Before you call Rheem or a technician
- Model and serial number (from the data plate on the side of the tank)
- The exact code(s), plus the alarm history from the menu
- Hot, lukewarm or cold water?
- What you've already tried (filter cleaned, condensate line cleared, power-cycled)
- Your original receipt: Rheem requires proof of purchase for warranty service
Phone numbers from the Gen V manual: Rheem national service: 1-800-432-8373 and EcoNet Wi-Fi/app support: 1-800-255-2388. Ask any technician to read the Service → Sensors screen and test parts with a meter before replacing a control board. Board swaps are expensive, and they're often not the real fix.
Rheem hybrid error code FAQ
How do I clear an alarm on a Rheem hybrid water heater?
Press Next until Current Alarm appears, scroll with the Down arrow, then press Clear Alarm. If the fault is still there, the code returns. Clearing a code only tells you whether your fix worked.
Why is my Rheem hybrid only running on the elements?
Either it's set to Electric mode, or a heat pump code is active (A004–A009, A101, A102, A105, A106 or A108). Check Current Alarm first, then check the mode.
How do I stop the beeping?
Change the ALARM BEEP setting from Yes to No. Write the code down first: muting the alarm doesn't fix anything.
Can I reset a Rheem hybrid by turning the breaker off and on?
Yes, a power cycle is a reasonable first step for board and clock codes (A502, A503, A9xx). It won't fix a real sensor, element or drainage fault, and the code will come back.
My Rheem shows A108 but there's no water anywhere. Why?
If the condensate line is clear and the pan under the filter is dry, the condensate sensor itself is probably faulty. That's a simple part swap for a technician.
Is E1, E2 or HP01 a Rheem hybrid code?
Not on US models. Those E, F and P codes belong to Australian Rheem heat pumps or other products. US hybrids use A- and T-codes.
Does the EcoNet app show error codes?
EcoNet-connected units can send leak and diagnostic alerts to your phone. Always confirm the four-character code on the unit's own display before you call.
How we checked this page
Code meanings, heating behavior, owner and technician steps, mode ratings, clearances, condensate rules, maintenance steps and phone numbers come from Rheem's Gen V Use & Care manual AP23657 Rev 01. Older code meanings come from Rheem manual AP16697. Element resistance and 208 V output figures are standard electrical calculations (resistance = volts² ÷ watts). Codes that appear only on third-party sites are not in our tables.