Rheem A108 Error (Condensate Blocked): What It Means and How to Fix It

By Hot Water Pump Repair Editorial Team · Checked against Rheem manual AP23657 Rev 01 and Rheem service bulletin TB 1332 · Last reviewed December 2026

Quick answer: A108 means water from the heat pump's condensate drain is backing up and has wet the condensate sensor (a rope-style sensor in the drain pan under the top cover). Your heater keeps making hot water, but it switches to its electric elements, the most expensive way to heat. In most cases the fix is a clogged or badly routed condensate line that you can clear yourself in 10–20 minutes. If the pan is dry and the line is clear, the sensor (or, rarely, the control board) is faulty.

10–20 min
typical DIY fix time for a clogged line
Hot water: yes
but on elements, so your bill goes up until it's fixed
Difficulty: easy
screwdrivers and a wet/dry vacuum; no electrical work

Which Rheem heaters show A108?

A108 is an alarm on Rheem and Ruud hybrid (heat pump) water heaters, including the ProTerra / Performance Platinum Gen V models covered by manual AP23657. In that manual, A108 reads "Condensate Blocked: Unclog Line", and the heater's heating source defaults to the electric elements while the alarm is active.

Check your product first. Rheem reuses code numbers across product lines, and on its gas and tankless products a similar-looking code can mean something unrelated. This guide is only for hybrid heat pump water heaters: the tall electric tank with a fan and filter on top. Not sure which generation you have? See our Rheem code generations table.

Why A108 happens: how the condensate system works

A heat pump water heater works like an air conditioner in reverse. It pulls heat out of the room air and puts it into the water. As the air cools across the cold evaporator coil, moisture in the air turns into water, just like the water that drips from a window AC. That water (condensate) collects in a small pan under the top cover and leaves through a drain line.

Rheem places a condensate sensor in that pan. If the drain can't keep up, water rises, the sensor gets wet, and the control board shows A108. It also stops the heat pump so it doesn't keep making water with nowhere to go. That's why the elements take over.

Why it often appears in summer: humid air produces much more condensate. A slow, partly clogged line that coped in winter can overflow in a humid July. That's also why basements and laundry rooms see this code most.

The 8 causes of A108, from most to least likely

#CauseHow to spot itWho fixes it
1Algae, slime or dust clog in the line or at the pan outletWater standing in the pan; slow or no drip at the drain endYou
2Line sags, kinks or runs uphillA dip in the hose holds water; line rises before it fallsYou
3Drain end is submerged (in a floor drain, bucket or sump)Hose outlet sits under water, so it can't drain freelyYou
4Condensate pump failed or unpluggedPump reservoir full, no hum, or float stuckYou (or replace the pump)
5Frozen line in a garage, crawl space or exterior wallCode appears on cold nights; uninsulated line in a cold spaceYou, then reroute or insulate
6Installation problem: no P-trap on a sewer tie-in, line too small, too long a horizontal runA108 started soon after installationInstaller
7Faulty condensate sensorPan is dry, line is clear, code still returnsTechnician
8Control board fault (rare)Code stays even with the sensor unpluggedTechnician

Rheem's own service bulletin for this alarm (TB 1332) lists the same three root causes in order of likelihood: a genuinely clogged drain line or pan, a defective condensate rope sensor (especially on new installations), and, less often, the control board.

How to fix A108, step by step

Safety: Turn the water heater off at the breaker before removing any cover. These units run on 240 volts. Don't open the sealed refrigerant section, and never poke wires or tools into the fan or coil.

What you need

Step 1: Write down the code, then turn off power

Note any other codes in the alarm list (press Next until "Current Alarm" appears on Gen V units). If you also see A107 (water on the floor), find the leak first. Then switch off the breaker.

Step 2: Follow the drain line to its end

Start at the condensate fitting near the top of the heater and trace the hose to where it empties. Look for:

Step 3: Vacuum the clog out (don't blow it in)

Hold the shop vac hose tightly over the drain end of the condensate line, sealing it with a rag, and run it for 30–60 seconds. Check the vacuum for slime or debris. Never blow compressed air back toward the heater: it can push the clog into the pan or wet the sensor even more.

Step 4: Check and clean the pan

Remove the top cover (usually a few screws). With a flashlight, look into the condensate pan:

Step 5: Flush and disinfect

Pour about a cup of bleach (or white vinegar) into the condensate opening, wait a few minutes, then pour in clean water and watch it run out the far end. Rheem recommends a cup of bleach once a year to stop algae, mold and mildew. Rheem also notes condensate isn't acidic and doesn't need a neutralizer.

Step 6: Dry the sensor, power up and clear the alarm

Let the wet sensor dry, or gently blot it. Refit the cover, restore power, and press Clear Alarm. Leave the heater in your normal mode (Energy Saver is the default) and check again over the next day. If A108 doesn't come back, you're done.

Step 7: If the pan is dry and A108 comes back

This points to the sensor or board. Rheem's service bulletin has technicians test by temporarily disconnecting the condensate sensor. If the alarm clears, the sensor is bad. If it stays, the control board is suspect. That test is inside the electrical compartment, so we recommend booking a technician for it (see "Before you call" below).

Quick diagnosis: what your pan tells you

💧 Pan has water, line is slow

Clog or bad routing. Clear the line (Steps 3–5) and fix any sag or submerged outlet.

❄️ Code only on cold nights

Frozen line. Thaw it, then insulate it or reroute it through a heated space.

✅ Pan dry, line clear, code returns

Faulty condensate sensor (most likely) or control board. Call a technician.

A108 vs A107: don't mix them up

A108A107
Display textCondensate Blocked: Unclog LineWater Detected on Floor: Check for Leaks
SensorInside the condensate pan (top of unit)Leak rope on the floor around the tank
Hot water?Yes, on elementsHeating stops (shut-off valve closes if fitted)
UrgencyFix within days; it costs moneyAct now; there may be an active leak

The two can appear together. If a clogged condensate line overflows onto the floor, the leak rope gets wet too. Rheem also warns that the condensate line must never drain into the water heater's own drain pan, because that will trigger the leak sensor.

Garage and cold-climate installs: stop A108 from freezing lines

A frozen condensate line is a common winter cause of A108, especially where the line runs along an outside wall, through a garage, or outdoors. To stop it coming back:

Installer checklist (what a correct condensate setup looks like)

If A108 appeared within weeks of installation, the routing is the first suspect. Here's what Rheem's manual calls for:

Pro tip: When you replace a hard PVC line, many owners and plumbers switch to clear vinyl tubing with a cleanout tee near the heater. You can see slime building up long before it blocks, and you can flush it in seconds.

What A108 costs you if you ignore it

With A108 active, your heater runs like an ordinary electric water heater. Rheem's own mode chart rates Electric mode "Very Low" for efficiency, compared with "Very High" for the default Energy Saver mode. In practical terms, a heat pump water heater typically uses a fraction of the electricity of its elements for the same hot water. A month on elements can noticeably raise your bill even though the showers feel normal. That's why A108 is worth fixing quickly, even though it isn't an emergency.

Prevent A108: a simple maintenance routine

Before you call Rheem or a technician

Phone numbers: the Gen V manual lists Rheem national service at 1-800-432-8373. Rheem also runs a hybrid technical services line at 1-800-995-0982. Ask the technician to check the pan and run the sensor-disconnect test before replacing a control board. The sensor is the far more common culprit.

Rheem A108 FAQ

Can I keep using hot water with A108?

Yes. The heater switches to its electric elements and keeps making hot water. It just costs more to run until you fix the drain.

Will A108 clear itself?

Sometimes the sensor dries out and the code stops. But if the line is still partly blocked, it will come back, often on the next humid day. Clear the line properly and then press Clear Alarm.

Can I use vinegar instead of bleach?

Yes. White vinegar is a gentler option for routine cleaning. Rheem's manual specifically suggests a cup of bleach once a year to control algae, mold and mildew. Never mix bleach and vinegar.

Do I need a condensate neutralizer?

No. Rheem notes that the condensate from its hybrid water heaters isn't acidic and doesn't need neutralizing. Neutralizers are for high-efficiency gas appliances.

Why did A108 start right after installation?

On new installs, the most common causes are routing problems (line runs uphill, sags, or ends under water) and, per Rheem's service bulletin, a faulty condensate sensor. Ask your installer to check both under their labor warranty.

Why does A108 keep coming back every summer?

Humid air means much more condensate. A line that is slightly undersized, too flat or partly clogged copes in dry months but overflows in summer. Flush it before summer, and improve the slope if needed.

How much does a technician charge to fix A108?

It depends on your area and the cause. Clearing a line is usually a short visit, while a sensor or control board replacement costs more for parts. If the heater is new, the fix may be covered by the installer's or Rheem's warranty, so check before paying.

How we checked this page

The alarm wording, heating behavior and technician steps come from Rheem's Gen V Use & Care manual AP23657 Rev 01, plus Rheem Technical Service Bulletin TB 1332 on the A108 alarm (causes, sensor-disconnect test and tools). Condensate routing rules (1/8 in. per foot slope, P-trap, condensate pump capacity, bleach treatment, no neutralizer, insulation) and the 37–145°F operating range come from Rheem's manual and spec sheet. Where we give general advice (vinyl tubing, shop-vac method, seasonal checks), it's standard plumbing practice, not a Rheem instruction.